INPUT |
Rated power |
400000VA |
Voltage |
380-400-415 Vac three-phase +N Vac |
Voltage tolerance |
400V +20% -25% |
Frequency tolerance |
± 2% (selectable from ± 1% to ± 5% from front panel) |
Soft start |
0 – 100% in 120” (selectable) |
BY PASS |
Rated voltage |
380-400-415 Vac |
Voltage tolerance |
± 15% (selectable from ± 5% to ± 25%) |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 5% (selectable from ± 0,25% to ± 10%) |
Number phases |
3 |
OUTPUT AND INVERTER OUTPUT |
Rated power |
400000VA |
Active power |
360000W |
Number phases |
3 |
Output current |
|
Crest factor (Ipeak/Irms) |
3 : 1 |
Waveform |
Sinewave |
Static stability |
± 1% |
Dynamic stability |
± 5% in 10 ms |
Frequency |
50 or 60 Hz selectable |
Voltage distortion with distorcing load |
<3% |
Voltage distortion with linear load |
<1% |
Overload |
125% 150% 168% of rated current for 60’/10’/1’ |
ENVIRONMENTAL |
Color |
Dark grey RAL 7016 |
Remote control |
ESD and bypass |
Communication |
Double RS232/C, slot for SNMP adpter and slot for voltage free contact |
Standard |
European Directives: L V 2006/95/CE low voltage directive EMC 2004/108/CE electromagntic compatibility Directive Standards: Safety IEC EN6240-1; EMC IEC EN62040-2 C2 Classification in accordance with IEC62040-3 (voltage Frequency Independent) VFI-SS-111 |
Protection rating |
IP20 |
Line-interactive/Smart Active efficiency |
>98% |
Noise |
< 70-72 dBA at 1m |
Remote signals |
Voltage free contacts |
Operating temperature |
0 ÷ 40 °C |
Relative humidity |
95% no condensing |
DATA |
Weight without internal batteries |
1700 Kg |
Dimensions (wxdxh) |
1500x1000x1900 |