INPUT |
Rated power |
12000VA |
Voltage |
230 Vac single-phase or 400 Vac three-phase +N Vac |
Voltage tolerance |
± 20% |
Frequency tolerance |
40/72 Hz |
Power factor |
0.99 |
BY PASS |
Rated voltage |
230 |
Voltage tolerance |
± 15% (selectable from ± 5% to ± 25%) |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 5% (selectable from ± 0,25% to ± 10%) |
Number phases |
1 |
OUTPUT AND INVERTER OUTPUT |
Rated power |
12000VA |
Active power |
10800W |
Number phases |
1 |
Output current |
55A |
Crest factor (Ipeak/Irms) |
3 : 1 |
Waveform |
Sinewave |
Static stability |
± 1% |
Dynamic stability |
± 3% in 10 ms |
Frequency |
50/60 Hz selectable |
Voltage distortion with distorcing load |
3% |
Voltage distortion with linear load |
1% |
Overload |
125% 150% 168% of rated current for 10’/1’/5 |
BATTERIES |
Type |
Maintenance-free sealed acid |
Typical recharge time |
6 h |
ENVIRONMENTAL |
Color |
Dark grey RAL 7016 |
Remote control |
ESD and bypass |
Communication |
Double RS232/C, slot for SNMP adpter and slot for voltage free contact |
Standard |
European Directives: L V 2006/95/CE low voltage directive EMC 2004/108/CE electromagntic compatibility Directive Standards: Safety IEC EN6240-1; EMC IEC EN62040-2 C2 Classification in accordance with IEC62040-3 (voltage Frequency Independent) VFI-SS-111 |
Protection rating |
3 |
AC/AC efficiency |
>94% |
Line-interactive/Smart Active efficiency |
>98% |
Noise |
|
Remote signals |
Voltage free contacts |
Operating temperature |
0 ÷ 40 °C |
Relative humidity |
95% no condensing |
DATA |
Weight without internal batteries |
110 Kg |
Dimensions (wxdxh) |
440x850x1320 |